Performance standard: IEC60269.6;GB/T13539.6
Rated voltage: DC 24V~1500V
Rated current: 1A-400A
Breaking capacity: see parameter list
Protection type: gPV
Installation mode: Circular tube with base; insertion for square tube
Features: Full range DC breaking fuse link, time constant T ≤ 3ms.
It applies to the overload and short-circuit protection for solar PV system protective battery pack, PV sub-array, PV array and PV inverter
Specification parameters of PV cylindrical cap PV fuse
Model | Rated Voltage (V) | Rated Current(A) | Dimension (mm) | Breaking capacity (kA) | Outline Drawing No. |
ΦD | L | H |
PV-1038 | 24-1000 | 1, 2, 3, 4, 5, 6, 8, 10, 12, 15 | 10.3 | 38 | 10.5 | ≥10 | Fig.1 |
PV-1451 | 24-1000 | 20, 25, 32 | 14.3 | 51 | 13.8 |
PV-1085 | 1500 | 1, 2, 3, 4, 5, 6, 8, 10 | 10.3 | 85 | 10.5 |
PV-22127 | 1500 | 10, 12, 16, 25 | 22.2 | 127 | 16.2 |
Specification parameters of PV square tube PV fuse
Model | Rated Voltage (V) | Rated Current(A) | Dimension (mm) | Breaking capacity KA | Outline Drawing No. |
A | B | C | D | E | H |
PV-1C | 1000 | 32, 40, 50, 63, 80, 100 | 70 | 135 | 48 | 62 | 20 | 6 | ≥50 | Fig.2 |
PV-2C | 1000 | 125, 160, 200, 250 | 70 | 150 | 58 | 72 | 25 | 6 |
PV-3C | 1000 | 315, 400, 500 | 70 | 150 | 67 | 82 | 32 | 6 |
PV-1C | 1500 | 32, 40, 50, 63, 80 | 120 | 185 | 48 | 82 | 20 | 6 |
PV-2C | 1500 | 100, 125, 160, 200 | 120 | 200 | 58 | 72 | 25 | 6 |
PV-5C | 1500 | 250, 315, 400 | 120 | 200 | 75 | 88 | 32 | 6 |