Main technical data
1. The fuse under specified operating conditions is able to reliably break any fault current from the minimum breaking current to the rated breaking current.
2. This product applies to the indoor AC 50 ~ 60Hz system.
3. Time - current characteristic curve, as shown in Fig. 2, Fig. 3 and Fig. 4, the part above the minimum breaking current is indicated with dotted line.
4. Current limiting characteristic curve is as shown in Fig. 5.
5. I2t characteristic curve is as shown in Fig. 6.
Fig. 2 XRNT3A-12 time - current characteristic curve

Fig. 3 XRNT3A-24 time - current characteristic curve
Fig. 4 XRNT3A-40.5 time - current characteristic curve
Fig. 5 XRNT3A current limiting characteristic curve

Fig. 6 XRNT3A I2t characteristic curve
Selection of fuse
General selection principle for primary fuse of transformer
Rated Voltage (kV) | Rated Capacity of Transformer (kVA) |
|
|
100 | 125 | 160 | 200 | 250 | 315 | 400 | 500 | 630 | 800 | 1000 | 1250 | 1600 | 2000 |
Rated Current of High-voltage Fuse (A) |
6/7.2 | 16 | 20 | 20 | 25 | 31.5 | 40 | 50 | 63 | 80 | 100 | 125 | 160 | 200 | 250 |
10/12 | 10 | 16 | 16 | 20 | 25 | 31.5 | 40 | 50 | 63 | 80 | 80 | 100 | 125 | 160 |
15/17.5 | 6.3 | 10 | 10 | 16 | 16 | 20 | 25 | 31.5 | 40 | 50 | 80 | 80 | 100 | 125 |
20/24 | 6.3 | 10 | 10 | 10 | 16 | 16 | 20 | 25 | 31.5 | 40 | 50 | 63 | 80 | 100 |
35/40.5 | 3.15 | 6.3 | 6.3 | 6.3 | 10 | 10 | 16 | 16 | 20 | 25 | 31.5 | 40 | 50 | 56 |
Outline drawing of non-standard fuse link
Fig. 7 XRNT3A-40.5/6.3A~50A
Fig. 8 XRNT3A-40.5/6.3A~50A